Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
39
The module update rate is determined by the number of channels enabled
and the filter frequencies selected. For example, if all 32 channels are
enabled and the filter frequency for all groups is 60 Hz, then the cycle
time for a full set of 32 channels is 32 x 58 msec or 1.856 seconds.
It takes four ladder logic scans of the eight registers to see all 32 chan-
nels. These four scans must be completed at least twice as fast as the
module update time to ensure no data is missed. In the example above
the ladder scan time would need to run at 1.856 sec/8 or 232 msec or
faster to ensure no data is missed.
The following ladder logic shows how to move data from the 8 multi-
plexed input words to a block of 32 output words starting at location
400101 using the autosequence mode. This example file for use only
with Modsoft programming software can be formed on the install disk
shipped with your module. The file is under the A:\Programs
subdirectory. To install:
1. Insert the install disk into drive A:
2. Copy A:\Programs\QAI32_AC.* C:\Modsoft\Programs
3. Select File QAI32_AC under Modsoft to run. The I/O map is as follows:
Rack Slot Module Input Ref Output Ref Description
1 03 ACI 051 00 3000001-3000009 4000001-4000001 ACI05100 AN IN 32CH
300009 300009 300009 300009 300001
NCBT NCBT NCBT NCBT
#00011 #00012 #00015 #00016 400101
BLKM
#00008
300009 300009 300009 300009 300001
NCBT NCBT NCBT NOBT
#00011 #00012 #00015 #00016 400109
BLKM
#00008
300009 300009 300009 300009 300001
NCBT NCBT NOBT NCBT
#00011 #00012 #00015 #00016 400117
BLKM
#00008
300009 300009 300009 300009 300001
NCBT NCBT NOBT NOBT
#00011 #00012 #00015 #00016 400125
BLKM
#00008