Spectrum-controls 140 EHC 204 00sc Manual do Utilizador

Consulte online ou descarregue Manual do Utilizador para Instrumentos de medida Spectrum-controls 140 EHC 204 00sc. Spectrum Controls 140 EHC 204 00sc User Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 0
Counter / Flow Meter Input Module
Cat. No. Quantum Automation Series
140 EHC 204 00sc - 4 Channel
140 EHC 208 00sc - 8 Channel
Installation Instructions
Owners Guide 0300185-01 Rev. A
Vista de página 0
1 2 3 4 5 6 ... 80 81

Resumo do Conteúdo

Página 1 - Installation Instructions

Counter / Flow Meter Input ModuleCat. No. Quantum Automation Series140 EHC 204 00sc - 4 Channel140 EHC 208 00sc - 8 ChannelInstallation InstructionsOw

Página 2 - Contents

Counter / Flow Meter Input Module11Hardware FeaturesThe Quantum counter module contains a removable Modicon 40-pin terminal block providing connection

Página 3

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc12Hardware DescriptionDoor (removable) Covers the terminal block and includes an identificati

Página 4

Counter / Flow Meter Input Module13Table 1-3 Blink Codes for Fault LEDCode (Number of Blinks) Error TypeOff No Faults1 Dual Port RAM fault.2 FPGA

Página 5 - Manual Contents

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc14 2ChapterInstallation and WiringThis chapter includes information about:• Module compliance

Página 6 - Related Documentation

Counter / Flow Meter Input Module15Low Voltage DirectiveThis product is tested to meet Council Directive 73/23/EEC Low Voltage, since it operates with

Página 7

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc16Reducing NoiseMost applications require installation in an industrial enclosure to reduce t

Página 8 - 1Chapter

Counter / Flow Meter Input Module17• Routing field wiring in a grounded conduit can reduce electrical noise.• If field wiring must cross AC or power c

Página 9 - Module Features

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc18Inserting the Module in the PLC RackDo the following to place the module in the PLC rack:1.

Página 10 - Hardware Features

Counter / Flow Meter Input Module19Removing and Replacing the Terminal BlockWhen wiring the module, it is not necessary to remove the terminal block.

Página 11 - Diagnostic LEDs

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc20Wiring the Terminal BlockThe module terminal block has eight shield terminals provided as f

Página 12 - Recommended Cables

Counter / Flow Meter Input Module3ContentsContentsContentsContentsContentsWWWWWhat this Guide Covers ...

Página 13 - 2Chapter

Counter / Flow Meter Input Module21Specification ValueWire Type Stranded, Cu-90°C (194°F)Wire Size 16 to 22 AWGTerminal Screw Torque 0.68 Nm (6 in-lb)

Página 14 - Installation Considerations

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc22CAUTION - Be careful when stripping wires. Wire fragments that fall into a module could ca

Página 15 - Selecting a Location

Counter / Flow Meter Input Module23 3ChapterModule ConfigurationThis chapter includes information on the following:• Module addressing• Setting up the

Página 16 - Module Installation

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc24Module AddressingThe module uses sixteen zoom (parameter) registers, nine 4X (output) regis

Página 17 - Field Wiring

Counter / Flow Meter Input Module25Setting Up the Configuration SoftwareThe module is compatible with several configuration software packages: ModSof

Página 18

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc26Setting Zoom Registers Using ModSoftThe procedure below tells how to enable the zoom regist

Página 19 - Wiring the Terminal Block

Counter / Flow Meter Input Module27Setting Zoom Registers Using ConceptThe next procedure describes how to enable the zoom registers and make configur

Página 20 - Wiring the Module for Inputs

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc28Setting Up SCIOCFG SoftwareVersion 2.1 of Concept introduced a tool for importing Modconne

Página 21

Counter / Flow Meter Input Module29Zoom Register LayoutThe following table shows the layout for each of the zoom registers. The 8 channel module use

Página 22 - 3Chapter

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc30Uni-DirectionalWith this configuration, the input increments in an upward direction. All 8

Página 23 - Module Addressing

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc4Making Bit Settings for Zoom Registers ...

Página 24 - Setting Up ModSoft

Counter / Flow Meter Input Module3130 kHz Filter, Bit 12The 30 kHz filter is recommended for counter or flow meter applications running at speeds less

Página 25 - Setting Up Concept

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc32Making Bit Settings for 4X RegistersYou can only set 4X register bits using ladder logic.

Página 26 - Up Concept

Counter / Flow Meter Input Module33Bank/Data Format Select: Bits 15-16The function of these two bits is determined by the Data Delivery Mode, Bit 14.I

Página 27 - Setting Up SCIOCFG Software

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc34Due to the limited register availability of the Quantum Platform, the scale and limit facto

Página 28 - Zoom Register Layout

Counter / Flow Meter Input Module35Counter Preset:This output data word is used in conjunction with the Counter Preset enable bit. When this bitis se

Página 29 - X4 Quadrature Encoder

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc36 R Rate Factor:The R scale factor can be used for scaling of the output frequency. The out

Página 30

Counter / Flow Meter Input Module37Preset, Bit 15Set bit 15 to 1 to load the counter preset value into the counter. This value is used to set thecoun

Página 31

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc38State, Bit 6”.ZeroFor the CounterIndicates when the count is zero. The status of the flag

Página 32

Counter / Flow Meter Input Module39Roll over to, Bit 7When the counter exceeds the maximum count or limit value it will roll over the top. When theco

Página 33 - Layout for 4X+1 Register

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc40Bit Settings for 3X+0 RegistersThe 3X+0 registers contain data, scaling and status informat

Página 34

Counter / Flow Meter Input Module5 K & M Factor Set Flag: Bit 3 ...

Página 35

Counter / Flow Meter Input Module41The process for updating the scale coefficients and the count limits is as follows:1. Set the Scale/Limit Word to i

Página 36

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc42The 3X registers (3X+1 through 3X+8) contain data and status information for channels 1thro

Página 37

Counter / Flow Meter Input Module43Counter Preset Flag: Bit 15When the Counter Preset value is reached this flag bit is set. The bit is reset when th

Página 38

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc44Counter Limit Flag: Bit 8This flag indicates that the counters accumulator has reached its

Página 39

Counter / Flow Meter Input Module45

Página 40 - Bit Settings for 3X Registers

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc46 4ChapterProgrammingWith configuration complete, it is time to prepare ladder logic to refl

Página 41

Counter / Flow Meter Input Module47Address Description300001 3x Register Counter card Configuration Word echo300002 3x+1 Register Channel Data word 13

Página 42

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc48Address Description400800 N/A Channel 7 Preset400801 N/A Channel 7 Count limit400802 N/A Ch

Página 43

Counter / Flow Meter Input Module49Example : Demultiplexing DataThe following ladder logic shows how to move data from the 4 multiplexed input words

Página 44

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc50General Programming ExamplesExample 1: Loading Scaling FactorsThe following sample ladder

Página 45 - 4Chapter

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc6PrefaceRead this preface to familiarize yourself with the rest of the manual. This preface c

Página 46

Counter / Flow Meter Input Module51Select Channel - Rungs 1 and 2 select and load the data for channels 1 and 2 respectively.Select Channel - Rungs 1

Página 47

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc52Select Channel: Rungs 1 and 2 select and load data for channels 5 and 6 respectivelySelect

Página 48

Counter / Flow Meter Input Module53Stop Ladder: Rung 1 stops the ladder after all the data has been loaded for channels 1-8Select Variable: Rungs 1,

Página 49 - General Programming Examples

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc54Select Variable: Rungs 1, 2 and 3 select one of the following variables: Preset, Count Li

Página 50

Counter / Flow Meter Input Module55Pass the variable to the counter card: Rung 1 loads the current variable (Preset, Count, Limit, Etc.) in to a temp

Página 51

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc56Sample ConfigurationSimple Bi-Directional Ring Counter:The figure below demonstrates ring c

Página 52

Counter / Flow Meter Input Module57Sample ConfigurationUsing the Meter Proving InputsA ball proving system would use the meter proving input found on

Página 53

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc58

Página 54

Counter / Flow Meter Input Module59 5ChapterMaintenance and DiagnosticsThis chapter describes maintenance and diagnostics for the Quantum counter modu

Página 55 - Ring Counter

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc60Standing Clear of the EquipmentWhen troubleshooting any system problem, have all personnel

Página 56

Counter / Flow Meter Input Module7Related DocumentationThe table below lists a number of reference documents that provide information to assist you wh

Página 57

Counter / Flow Meter Input Module61Internal DiagnosticsThe module performs internal diagnostics at both the module and channel levels of operation. W

Página 58 - 5Chapter

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc62Startup TestingThis section presents testing procedures recommended for use at module start

Página 59 - Preventive Maintenance

Counter / Flow Meter Input Module63Health Status Test (Concept)1. In Concept, access the I/O configurator and ensure that the module description, slot

Página 60 - Internal Diagnostics

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc64Active LED Does Not IlluminatePossible CausesThe module is not communicating with the PLC r

Página 61 - Startup Testing

Counter / Flow Meter Input Module65Corrective ActionIf necessary, install a pull-down resistor between the channel input and channel common or a pull-

Página 62 - Troubleshooting

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc66IndexIndexIndexIndexIndexNumericsNumericsNumericsNumericsNumerics24V gate enable24V gate en

Página 63 - No Signal Indication

Counter / Flow Meter Input Module67errors 1-11, 5-12verification 4-4confconfconfconfconfiguriguriguriguriguraaaaation ertion ertion ertion ertion errr

Página 64

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc68critical 5-9data definition 5-10extended error information field 5-11general common hardwar

Página 65 - IndexIndex

Counter / Flow Meter Input Module69KKKKKK or M scale factor stateK or M scale factor stateK or M scale factor stateK or M scale factor stateK or M sca

Página 66

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc70OOOOOoperationoperationoperationoperationoperationmodule 1-7system 1-11output routput routp

Página 67

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc8

Página 68

Counter / Flow Meter Input Module71rrrrremoemoemoemoemoving module frving module frving module frving module frving module from rom rom rom rom racaca

Página 69

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc72unidirunidirunidirunidirunidirectional operectional operectional operectional operectional

Página 70

Counter / Flow Meter Input Module73GlossaryThe following terms and abbreviations are used throughout this manual.A/D converter  The analog-to-digital

Página 71 - ModSoft 3-10

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc74input data scaling  Data scaling that depends on the data format selected for a channel co

Página 72 - Glossary

Counter / Flow Meter Input Module75

Página 73

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc76 AAppendixSpecificationsThis appendix lists the specifications for the Quantum counter modu

Página 74

Counter / Flow Meter Input Module77Electrical Fast Transient IEC 801-4Radiated Emissions CISPR 11 Class ASurge Impulse IEC 801-5Conducted Immunity IEC

Página 75 - AAppendix

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc78Input Protection Max. input voltage ±75VDC continuous, 106VAC peakMax. input current less t

Página 76 - Electrical Specifications

Counter / Flow Meter Input Module79

Página 77 - Standards Compliance

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc80

Página 78

Counter / Flow Meter Input Module9 1ChapterOverviewThis chapter describes the 4- or 8-channel Quantum Counter/Flow Meter input module (called Quantum

Página 79

Spectrum Controls SupportIf you need technical assistance, please review the information in chapter 5, “Maintenance and Diagnostics.”If you still have

Página 80 - Declaration of Conformity

The Schneider Alliances logo is a trademark of Schneider Electric. ©2001 Spectrum Controls, Inc. All rights reserved. Printed in U.S.A.Specifications

Página 81 - 01 Rev. A

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc10The modules flow meter mode is compatible with a variable reluctance AC input, which count

Modelos relacionados 140 EHC 208 00sc

Comentários a estes Manuais

Sem comentários